Electricity Meter Types and Wiring Methods

I. Single-Phase Electricity Meters

Single-Phase Direct: This is the simplest type of meter wiring, but it is also divided into jump-in and parallel-in. Opening the meter's junction box reveals four terminals: 1, 2, 3, and 4.

Jump-in: 1 is the incoming live wire, 2 is the incoming neutral wire, 3 is the outgoing live wire, and 4 is the outgoing neutral wire.

Electricity Meter Types and Wiring Methods图片1.webp

Bypass: 1 is the incoming live wire, 2 is the outgoing live wire, 3 is the incoming neutral wire, and 4 is the outgoing neutral wire.

Electricity Meter Types and Wiring Methods图片2.webp

Single-phase Mutual Inductor Type:

With a connector: The live wire is connected to transformer K1 and connected in parallel to the meter's input terminal 1. K1 is then connected in parallel to the live wire wrapped around the transformer's connection. K2 is connected to the neutral wire input terminal 3, and the neutral wire output terminal 4.

Without a connector: K1 is connected to meter terminal 1, K2 to meter terminal 3, the live wire is connected to terminal 2, the neutral wire to terminal 4, and the live wire is wrapped around the transformer output terminal to the load.

Electricity Meter Types and Wiring Methods图片3.webp

II. Three-phase Meter

Three-phase, four-wire direct-entry type: The meter has seven terminals: three live wire input terminals (1, 3, and 5), three live wire output terminals (2, 4, and 6), and one neutral terminal (7).

Electricity Meter Types and Wiring Methods图片4.webpElectricity Meter Types and Wiring Methods图片5.webp

Three-phase Mutual Inductor Type: When the metering load is large and the direct-entry method cannot meet the requirements, a mutual inductor method is required. The specific wiring configuration is as follows: Connect terminals 1, 4, and 7 to the S1 terminals of the A, B, and C transformers, respectively; connect terminals 3, 6, and 9 to the S2 terminals of the A, B, and C transformers, respectively; and connect terminals 2, 5, and 8 to the A, B, and C power supplies, respectively. Pass the A, B, and C power supply cables through the center of the transformers, and connect the S2 terminals of all three transformers to ground.

Electricity Meter Types and Wiring Methods图片6.webpElectricity Meter Types and Wiring Methods图片7.webp

For more detailed wiring diagrams or operating instructions, it is recommended to consult a professional electrician or refer to the meter's manual.

Wuxi Zhongyi Smart Technology Co., Ltd. focuses on the development and manufacturing of smart water meters, energy meters, gas meters, covering more than 90 countries around the world. If you are interested in smart water meters, Electricity meter and gas meters,please contact Zhongyi Smart!

www.zhongyismart.com

Wuxi Zhongyi smart Technology Co., Ltd. from the Internet of things water, electricity, gas, heating meter design and manufacturing, integrated energy remote meter reading and big data management analysis system research and development design.
Copyright © 2025 Wuxi Zhongyi Smart Technology Co., Ltd.
Add: Building 28, Zone B, GLPI-Park, No. 15 Hanjiang Road, Xinwu District, Wuxi City, Jiangsu Province,China
Tel: +86-0510-88717081Wechat:+8618661076788|Whatsapp:+8618661076788
Email: jeffzou@ucskype.com
Website: www.zhongyismart.com